Home / Products / Toroid transformers - 50/60Hz / Open Version Toroidal Transformer / Toroids 50-200VA, Low Voltage Lighting
Toroids 50-200VA, Low Voltage Lighting
| High quality open style toroidal transformers with a 230V a.c. 50/60Hz primary winding. Suitable for 12V a.c. low voltage lighting applications. |
![]() |
Product information and technical data
High quality open style toroidal transformers with a 230V a.c. 50/60Hz primary winding.
Suitable for 12V a.c. low voltage lighting applications.
Under no circumstances should both ends of the fixing bolt contact a metal chassis or frame as this would create a "shorted turn" causing irreparable damage.
Suitable for 12V a.c. low voltage lighting applications.
![]() |
![]() |
![]() |
![]() |
|||||
|
![]() |
|||||||
| Rated VA | Part Number | Regulation % Typical | Temperature Rise [K] | Dimensions* Diameter [mm] | Height [mm] | Weight Kg] |
| 50 | 91931-P1S1 | 15 | 46 | 80 | 33 | 0.65 |
| 105 | 91932-P1S1 | 11 | 49 | 93 | 46 | 1.05 |
| 150 | 91933-P1S1 | 8.5 | 48 | 105 | 42 | 1.35 |
| 200 | 91934-P1S1 | 7.6 | 51 | 105 | 50 | 1.75 |
- * Allow extra 4mm for mounting kit; allow extra 5mm where leads emerge.
- Leads: PVC insulated 150mm long.
- Maximum ambient operating temp. +40°C
- UL recognised for Insulation Class A (105°C)
- Meets all requirements of Class E (120°C)
- Neoprene pads: 5 KV isolation
Important Installation Note
Each transformer is supplied with a dished washer and protection pads for single hole fixing. Ensure that the pads are fitted above and below the transformer winding and that the dished washer is on top of the upper pad. Do not over tighten the fixing bolt (not supplied) as this could damage the winding.Under no circumstances should both ends of the fixing bolt contact a metal chassis or frame as this would create a "shorted turn" causing irreparable damage.